Upper Communication Unit for Digital Sensors SC-GU1-485
Download
-
Basic Information
-
Applications
-
Order guide
-
Option
-
Specifications
-
Dimensions
-
Cautions For Use
Basic Information
Proposal of a new "management and setting" method for sensors
Features
Control and settings can be carried out remotely
Setting and checking incident light intensity for digital sensors FX-501(P), FX-502(P),
LS-501(P)/403, DPS-401(P)/402(P) and analog input unit SC-A01/A02, SC-T1JA that are scattered inside and outside equipment can be carried out remotely for all sensors by using the SC-GU1-485, which greatly improves ease of operations such as monitoring equipment that is running and also equipment starting and maintenance.

Note:
Used when the output signal is sent via a SC-GU1-485 to the PLC.
If the output signal is sent directly to the PLC, a quick-connection cable(sub cable) (CN-72-C□, CN-71-C□) should be used.
High general applicability so that any type of PLC can be used
RS-485 communication provides a high level of general compatibility so that any type of PLC can be used.
Integration with existing systems is possible without the need to change PLCs.

Features
* The maximum number of units is 12 for configurations including either the FX-501(P)/502(P) or LS-501(P).
- Control and settings can be carried out remotely
- High general applicability so that any type of PLC can be used
- Communication speed 57.6 kbps Series connection of a maximum of 31 nodes is possible
- Up to 16 digital sensors* can be connected side by side
- Save wiring, construction and space
Applications
Centralized control and setting of scattered digital sensors (FX-301/305) is possible using a PLC or personal computer.

Order guide
System configuration

Notes:1) The maximum number of units is 12 for configurations including either theFX-501(P)/502(P)orLS-501(P).2) Used when the output signal is sent via aSC-GU1-485to the PLC.3) Use when wiring output signal lines directly to a PLC. For more information on quick-connection cables, refer tothe instruction manualor this page on the digital sensors used in your environment such as forFX-501(P)/502(P).
Communication unit
| Designation | Model No. | Description |
|---|---|---|
| Main unit | SC-GU1-485 | By the RS-485 communication, centralized control and setting of the individual digital sensors(FX-501/502, LS-403, DPS-401/402) are possible using a PLC or a PC. One unit can connect up to 16 digital sensors.(Note) |
Note : Maximum of 12 units in case of including the FX-500 / LS-500 series.
End plate
End plate is not supplied with the communication unit. Make sure to order it separately.
| Designation | Model No. | Description |
|---|---|---|
| MS-DIN-E | When SC-GU1-485, a sensor amplifier, an analog input unit or an end unit are connected on a DIN rail, these end plates clamp amplifiers into place on both sides. Make sure to use end plates when cascading multiple amplifiers together. 2 pcs. per set |
Option
| Designation | Model No. | Description |
|---|---|---|
| Wire-saving connector | CN-701 | Used when the output signal is sent via a SC-GU1-485 to the PLC, etc. |
Accessories
- SC-GU1-EU (End unit)
- SC-GU1-CC02 (Link cable)
- CN-73-C2 (Quick-connection cable)

CN-701 (Wire-saving connector)

Specifications
| Type | Main unit | |
|---|---|---|
| Model No. | SC-GU1-485 | |
| Applicable regulations | CE Marking (EMC Directive, RoHS Directive) | |
| Applicable digital sensor / input unit | FX-501(P), FX-502(P), LS-501(P), LS-403, DPS-401(P), DPS-402(P), SC-A01, SC-A02, SC-T1JA | |
| Connectable units | Max. 16 units of digital sensor / analog input unit per SC-GU1-485 (Note 2) | |
| Connectable nodes | Max. 31 nodes | |
| Supply voltage | 24 V DC ±10 % Ripple P-P 10 % or less | |
| Current consumption | 45 mA or less (SC-GU1-EU: 10 mA or less) | |
| Communication method | Two-wire half duplex communication | |
| Communication speed | 57,600 bps / 38,400 bps / 19,200 bps / 9,600 bps, Selectable by DIP switch | |
| Synchronization method | Asynchronous communication method | |
| Electrical characteristic | Conforming to EIA RS-485 | |
| Total extension length | Communication cable: 100 m 328.084 ft or less [SC-GU1-485 (termination) to PLC] Power supply cable: Less than 10 m 32.808 ft | |
| Indicators | Power (POWER) | Green LED (Lights up when the power is ON) |
| Communication (COMM) | Green LED (Lights up during communication) | |
| Upper communication error (C.Err) | Red LED [Blinks when communication error between PLC (Programmable Logic Controller) and Master or Master and Slave, or command error occurs] | |
| Lower communication error (S.Err) | Red LED (Blinks when communication error between the main unit and sensors occur) | |
| Ambient temperature | –10 to +55 ℃ +14 to +131 ℉ (If 4 to 7 units are connected in cascade: –10 to +50 ℃ +14 to +122 ℉, if 8 to 16 units are connected in cascade: –10 to +45 ℃ +14 to +113 ℉) (No dew condensation or icing allowed), Storage: –20 to +70 ℃ –4 to +158 ℉ | |
| Ambient humidity | 35 to 85 % RH, Storage: 35 to 85 % RH | |
| Voltage withstandability | 1,000 V AC for one min. between all supply terminals connected together and enclosure | |
| Insulation resistance | 20 MΩ, or more, with 250 V DC megger between all supply terminals connected together and enclosure | |
| Vibration resistance | 10 to 150 Hz frequency, 0.75 mm 0.030 in or maximum acceleration 49 m/s2 double amplitude in X, Y, and Z directions for 2 hours each | |
| Shock resistance | 98 m/s2 acceleration (10 G approx.) in X, Y and Z directions five times each | |
| Material | Enclosure: Heat-resistant ABS, Connector cap: silicone rubber | |
| Weight | Net weight : 35 g approx. (SC-GU1-EU: 10 g approx.), Gross weight: 120 g approx. | |
| Accessories | SC-GU1-EU (End unit): 1 pc. CN-73-C2 [Quick-connection cable (cable length 2 m 6.562 ft)]: 1 pc. SC-GU1-CC02 [Link cable (cable length 0.2 m 0.656 ft)]: 1 pc. | |
Notes:
1) Where measurement conditions have not been specified precisely, the conditions used were an ambient temperature of +20℃ +68℉
2) The maximum number of units is 12 for configurations including either the FX-501(P)/502(P) or LS-501(P).
Dimensions
- Unit: mm in
SC-GU1-485
Main unit

SC-GU1-EU
End unit (Accessory)

SC-GU1-CC02
Link cable (Accessory)

CN-73-C2
Quick-connection cable (Accessory)

CN-701
Wire-saving connector (Optional)

MS-DIN-E
End plate (Optional)

Material: Polycarbonate
Cautions For Use
- Never use this product in a device for personnel protection.
- In case of using devices for personnel protection, use products which meet laws and standards, such as OSHA, ANSI or IEC etc., for personnel protection applicable in each region or country.
- For communication conditions and commands of SC-GU1-485, refer to “Product specifications”.
- This product has been developed / produced for industrial use only.
- This product is suitable for indoor use only.
- Do not use during the initial transient time (1 sec.) after the power supply is switched on.